Specifications
Input voltage range
Input frequency range
Overload capacity
Temperature influence
Humidity influence
Influence of power supply voltage
Influence of power supply frequency
Influence of input frequency
Applicable
standards
Conforming standards
EMC
Safety standards
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Degree of protection
K8AB-PH
200 to 500 VAC
45 to 65 Hz
Continuous input: 115% of maximum input, 10 s max.: 125% of maximum input
Operating time
Fluctuation based on measured value at standard temperature:
20°C to standard temperature: ±10% max.
Standard temperature to 60°C : ±10% max.
(Humidity: 25% to 80%)
Operating time
Based on ambient room humidity
25% to 80%: ±10% max.
Operating time: ±10% max.
Note: The error in the operating value and operating time under standard conditions.
Operating time: ±10% max. (at 45 to 65 Hz)
Note: The error in the operating value and operating time under standard conditions.
At 45 to 65 Hz
Operating time ±10% max.
Note: The error in the operating value and operating time under standard conditions.
EN60255-5 and EN60255-6
Installation environment (Pollution Degree 2, Overvoltage Category III)
EN61326
UL508
20 MΩ min.
Between external terminals and case
Between input terminals and output terminals
2,000 VAC for one minute
Between external terminals and case
Between input terminals and output terminals
1,500 V power supply terminal common/normal mode
Square-wave noise of ±1 μs/100 ns pulse width with 1-ns rise time
Frequency 10 to 55 Hz, 0.35-mm single amplitude, acceleration 50 m/s2
10 sweeps of 5 min each in X, Y, and Z directions
100 m/s2, 3 times each in 6 directions along three axes (up/down, left/right, forward/backward)
Terminal section: Finger protection
Connections
Wiring Diagram
Phase Sequence and Phase Loss Operation Diagram
Phase Loss Operation
L1
Input L2
L3
Phase Sequence Operation
L1 L3 L1
L3 L2 L2
L2 L1 L3
Relay
Note: 1. Motor load phase loss cannot be detected. To detect motor load
phase loss, use the K8AB-PM or K8AB-PA.
2. The K8AB-PH output relay is normally operative.
3. L1 and L3 function both as the power supply terminals and as input
terminals. If the voltage drops below the minimum input voltage (60%),
then the Relay will not operate due to an undervoltage.
4. Phase loss is detected based on the phase sequence, so phase loss
cannot be detected for loads that generate inductive power, e.g., due
to motor during operation.
5. Phase loss is detected based on voltage, so phase loss cannot be
detected on the load side.
L1 L2 L3
Voltage input
L1
L2
L3
14
Signal output
12
11
Relay signal
output
Load
3