datasheetbank_Logo
数据手册搜索引擎和 Datasheet免费下载 PDF

K8AB-PW 查看數據表(PDF) - OMRON Corporation

零件编号
产品描述 (功能)
比赛名单
K8AB-PW
Omron
OMRON Corporation Omron
K8AB-PW Datasheet PDF : 10 Pages
1 2 3 4 5 6 7 8 9 10
Operation and Setting Methods
K8AB-PW
Connections
1. Input
Connect to L1, L2, and L3 (for three-phase three-wire mode) or L1, L2, L3, and N (for three-phase four-
wire mode), depending on the mode selected using pin 2 on the DIP switch.
The Unit will not operate correctly if the DIP switch setting and the wiring do not agree.
Make sure the phase sequence is wired correctly. The Unit will not operate normally if the phase
sequence is incorrect.
2. Outputs
Terminals 11, 12, and 14 are the output terminals for overvoltage (SPDT).
Terminals 21, 22, and 24 are the output terminals for undervoltage (SPDT).
N L1 L2 L3
Voltage input L1
L2
N
L3
14
Signal output
12
11
Overvoltage
alarm
24
Signal output
22
21
Undervoltage
alarm
Load
DIP Switch Settings
The Startup lock time, number of wires, and rated voltage are set using the DIP switch located on the bottom of the Unit.
DIP Switch Functions
ON
K8AB-PW1
OFF
SWITCH
ON
4
3
2
1
ON
SW1
SW2
SW3
SW4
DIP switch
Power ON lock time 5 s
OFF OFF
---
---
---
1s
---
---
---
Number of wires Three-phase, four-wire
---
---
---
Three-phase, three-wire
---
---
---
Rated voltage
Three-phase, Three-phase,
three-wire four-wire
240 V
138 V
---
---
230 V
133 V
---
---
220 V
127 V
---
---
200 V
115 V
---
---
Note: All pins are set to OFF at the factory.
K8AB-PW2
SWITCH
ON
4
3
2
1
ON
OFF OFF
Power ON lock time 5 s
---
---
---
1s
---
---
---
Number of wires Three-phase, four-wire
---
---
---
Three-phase, three-wire
---
---
---
Rated voltage
Three-phase, Three-phase,
three-wire four-wire
480 V
277 V
---
---
415 V
240 V
---
---
400 V
230 V
---
---
380 V
220 V
---
---
Note: All pins are set to OFF at the factory.
7

Share Link: 

datasheetbank.com [ Privacy Policy ] [ Request Datasheet ] [ Contact Us ]